Frequency converters are so common now that they are often treated as a dial that makes a motor go slower. What happens inside is considerably more interesting than that, and knowing it explains most of the practical questions that come up on site, from why torque falls above base speed to why a long motor cable causes trouble.
Three stages, one job
Almost every industrial converter follows the same architecture. A rectifier turns the incoming alternating supply into direct current. A capacitor bank, called the DC link, smooths that direct current and stores energy. An inverter stage then switches that direct voltage on and off very rapidly to synthesise a new alternating supply at whatever frequency and voltage the control demands.
The motor never sees the incoming mains at all. It sees only what the inverter produces, which is why a converter can change frequency freely and why the supply side and motor side of a drive behave as two almost separate electrical worlds.
Why frequency and voltage move together
Motor torque depends on the magnetic flux in the air gap, and that flux is set by the ratio of applied voltage to frequency. Reduce frequency without reducing voltage and the flux rises, saturating the iron and drawing enormous magnetising current. Reduce voltage without reducing frequency and the flux collapses, and with it the torque.
So a converter holds the ratio roughly constant as it changes speed. A 400 volt 50 hertz motor is driven at 200 volts when running at 25 hertz, keeping 8 volts per hertz in both cases. This is where the term volts per hertz control comes from, and even sophisticated vector control schemes are managing the same underlying relationship.
Constant torque below base speed, constant power above it
The consequence of holding the ratio constant is that the motor can produce full rated torque at any speed from standstill up to its base speed, which is normally the nameplate frequency. This is the constant torque region and it is where the vast majority of applications operate.
Above base speed, the converter cannot raise voltage any further because it is limited by the DC link, which in turn is limited by the incoming supply. Frequency keeps rising while voltage stays fixed, so flux falls and available torque falls with it. Power stays approximately constant instead. Running a 50 hertz motor at 75 hertz gives about two thirds of rated torque.
This is why a fan can often be run above 50 hertz without trouble, since fan torque demand falls as speed falls and the converter has margin, while a conveyor asked to run fast and pull hard at the same time will not.
The energy saving is a property of the load, not the drive
Converters are frequently sold on energy saving, and on the right load the saving is genuinely large. The reason has nothing to do with the converter being efficient and everything to do with the physics of centrifugal loads.
Flow through a pump or fan is proportional to speed. Pressure is proportional to speed squared. Power is proportional to speed cubed. Reduce speed to 80 percent and the power demand falls to roughly half. Reduce it to 50 percent and power falls to around an eighth.
That relationship is why throttling a valve or closing a damper is such a wasteful way to control flow. The machine still turns at full speed and full power while the restriction burns the excess as pressure drop and noise. Replacing that restriction with speed control captures the difference.
On a constant torque load such as a conveyor, a positive displacement pump or an extruder, no such relationship exists. Halving the speed roughly halves the power, which is proportional rather than dramatic. Converters on these loads are justified by process control, not by energy.
What the inverter output really looks like
The inverter does not produce a smooth sine wave. It produces a rapid series of voltage pulses of varying width, and the motor winding, being inductive, smooths those pulses into something close to a sinusoidal current. The voltage at the motor terminals remains a train of steep edged pulses.
Modern switching devices produce very fast rising edges, which is good for efficiency and bad for everything else connected to the motor. Those fast edges are the origin of three well known side effects.
Reflected wave phenomena occur when the cable between drive and motor is long enough that a pulse reflects from the motor terminals and superimposes on the incoming pulse. The resulting overvoltage can approach twice the DC link voltage and stresses the first turns of the winding hardest. Motors sold as inverter duty carry reinforced insulation for this reason.
Bearing currents arise because the fast switching produces a common mode voltage that can discharge through the bearing, pitting the raceway. The classic symptom is a fluted bearing surface and a motor that becomes noisy after a year or two. Insulated bearings, shaft grounding rings and symmetrical shielded cable all address it.
Electromagnetic interference is the third. The same fast edges radiate, and unshielded motor cable run alongside signal cable is a reliable way to corrupt analogue measurements.
What the drive does to the incoming supply
The rectifier at the front end draws current in short pulses around the peaks of the supply waveform rather than smoothly. That pulsed current is rich in harmonics, predominantly the fifth, seventh, eleventh and thirteenth.
Harmonic currents cause additional heating in transformers and cables, can overload power factor correction capacitors and distort the supply voltage for other equipment. On a site with one small drive this is irrelevant. On a site where converters make up a large share of the total load it is a design issue that needs line reactors, harmonic filters or an active front end.
Cooling the motor at low speed
A standard motor cools itself with a fan on its own shaft. Run it slowly and the fan turns slowly, so cooling falls just as fast as speed while the current, on a constant torque load, does not fall at all.
The practical outcome is that a self ventilated motor on a constant torque load cannot be run continuously at very low speed without either derating or forced ventilation. Manufacturers publish derating curves for exactly this, and ignoring them is one of the most common causes of failure on converter retrofits.
What to take from all this
A frequency converter is not a speed dial bolted onto an existing system. It replaces the supply the motor sees, and the motor, the cable, the bearings and the upstream network all experience something different as a result.
None of these effects are reasons to avoid converters. They are reasons to specify shielded cable of appropriate length, to consider inverter rated motors on new installations, to check derating at low speed and to think about harmonics when converters become a large fraction of site load. Handled at design stage, all of them are routine.