Selecting a frequency converter looks like it should be trivial. The motor is 22 kilowatts, so the drive is 22 kilowatts. That approach works often enough to feel safe and fails often enough to be worth replacing with something more deliberate.
Drives deliver current, not kilowatts
The kilowatt figure on a converter is a marketing convenience. It describes the drive paired with a typical four pole motor of that rating under normal duty. What the converter is physically limited by is output current, because current is what heats the switching devices.
So the first rule is to size from the motor nameplate current, not from its power. Two motors of the same kilowatt rating can have noticeably different rated currents depending on pole count, voltage, efficiency class and power factor. A two pole high efficiency machine and an eight pole machine of the same power are not interchangeable from the drive’s point of view.
This matters most for machines that are not standard induction motors. Synchronous reluctance machines have lower power factor and higher current for the same output, and a drive selected on kilowatts alone will be undersized.
Normal duty and heavy duty are different ratings of the same hardware
Most manufacturers publish two current ratings for each drive. Normal duty, sometimes called variable torque, allows a modest overload, typically around 110 percent for one minute in every ten. Heavy duty, sometimes called constant torque, allows a much larger overload, typically 150 percent for one minute in every ten.
The same physical drive carries both ratings. Choosing heavy duty simply means accepting a lower continuous current so that headroom remains available for overload. In practice this usually means selecting one frame size larger than the motor power would suggest.
Which rating applies is decided by the load, and this is where the real sizing decision lies.
Variable torque loads
Centrifugal pumps, fans and blowers are variable torque loads. Torque demand rises with the square of speed, so at low speed the load is very light and the drive never sees a large overload. Breakaway torque is low because there is nothing holding the impeller still.
For these applications the normal duty rating is appropriate, and a drive matched to motor power on that basis is normally correct. The saving in drive size compared with heavy duty selection is real and legitimate.
The exception is the pump that must start against a static head with a non return valve holding pressure, or a large centrifugal fan with a heavy impeller and very high inertia. Inertia does not appear in the torque curve at all, and accelerating a large fan in a reasonable time can demand far more torque than steady running ever does.
Constant torque loads
Conveyors, extruders, mixers, positive displacement pumps, hoists, crushers and most machine tools demand roughly the same torque at every speed. A loaded conveyor needs as much torque to move slowly as it does to move quickly.
These loads require the heavy duty rating, because breakaway torque is high and because the drive has to be able to deliver it at low speed where the motor has no back electromotive force to help. A conveyor that has been standing loaded overnight may need 150 percent of rated torque to break away, and a drive sized on normal duty simply trips.
The same applies to any load that can jam. A mixer in thickening product, a crusher taking an oversized lump or a hoist with a mechanical obstruction all present sudden torque demands that a marginally sized drive cannot ride through.
Inertia and acceleration time
Torque required to accelerate a load is the inertia multiplied by the rate of change of speed. A large fan impeller, a flywheel, a centrifuge basket or a long conveyor all carry substantial inertia, and the acceleration torque can dominate the sizing calculation.
The practical lever is time. Doubling the permitted acceleration time halves the acceleration torque. Where the process tolerates a slower start, extending the ramp is usually far cheaper than buying a larger drive. Where it does not, the inertia has to be included in the calculation explicitly.
This is also where drives are most often undersized in practice, because inertia is invisible on a nameplate and easy to leave out.
The environmental deratings that get forgotten
Published drive ratings assume a reference ambient, usually 40 degrees Celsius, an altitude up to 1000 metres and a specific switching frequency.
Each of those carries a derating. Higher ambient reduces permitted current, which matters because drives frequently sit in sealed control cabinets where the internal temperature is well above the room. Altitude reduces cooling and dielectric strength. Raising switching frequency to reduce audible motor noise increases losses in the drive and can cost a significant share of its rated output.
A drive selected correctly on paper and then installed in a hot cabinet with switching frequency raised for noise can end up genuinely undersized without anything obvious having changed.
Cable length and output filtering
Long motor cables increase capacitive current that the drive must supply in addition to the motor current, and they raise the risk of reflected wave overvoltage at the motor terminals. Manufacturers state maximum cable lengths for shielded and unshielded cable, and exceeding them requires an output reactor or a sine filter.
Those filters also consume voltage, which reduces the voltage available at the motor and therefore its torque. If a sine filter is needed, its effect belongs in the sizing calculation rather than being added afterwards.
A workable sizing sequence
Take the motor rated current from the nameplate rather than the drive catalogue. Decide whether the load is variable or constant torque and select the corresponding duty rating. Establish the maximum torque the load will ever demand, including breakaway and acceleration, and express it as a percentage of motor rated torque. Confirm the drive can supply that percentage for long enough.
Then apply deratings for cabinet ambient, altitude and switching frequency, and check cable length against the manufacturer’s limit. If any of those deratings bites, step up a frame size rather than hoping.
The cost difference between one drive frame and the next is small compared with a production stoppage caused by nuisance tripping, and considerably smaller than the cost of discovering the problem after commissioning. Where the application is genuinely borderline, it is worth confirming the selection against the frequency converter ratings published for the specific series rather than relying on a generic kilowatt match.