Measuring real motor load before you buy a replacement

Almost every decision about a motor depends on knowing what load it actually carries. Whether to replace it, what size to replace it with, whether an efficiency upgrade pays, whether a converter is worthwhile. The load factor is the input to all of them, and it is usually estimated rather than measured.

Why estimating fails

The natural assumption is that a motor selected for a machine is roughly matched to it. In practice, margins accumulate through design, procurement and replacement history, and it is common to find motors running at half of what their nameplate suggests or less.

The second assumption, that current is proportional to load, is also wrong, and it is wrong in a direction that makes motors look more heavily loaded than they are. Magnetising current flows regardless of load, so a motor at half load draws well above half current.

Both assumptions push decisions towards buying the same size again, which is exactly what perpetuates the problem.

Method one, input power measurement

This is the most accurate approach available without specialist equipment. A three phase power meter or power quality analyser measures true input power in kilowatts, accounting for power factor and waveform distortion.

Load factor is then the measured input power multiplied by the motor efficiency, divided by the rated output power. Efficiency at the operating point is needed, and since that depends on the load you are trying to find, one iteration usually suffices. Start with the rated efficiency, calculate the load, look up efficiency at that load, and recalculate.

The method works on any motor, including those on frequency converters, provided the measurement is taken on the motor side of the drive with an instrument capable of handling the switched waveform. Measuring on the supply side of a converter gives drive input power, which includes drive losses and tells you something different.

The main practical requirement is access to the motor terminals or the starter, and the willingness to log over a representative period rather than reading once.

Method two, current measurement with correction

A clamp meter on each phase is quick, needs no connection and can be done during normal operation.

The raw ratio of measured current to rated current overstates the load. A usable correction is to treat the relationship as approximately linear between the no load current and the rated current, rather than between zero and rated.

No load current is typically 25 to 40 percent of rated current for a medium sized motor, higher for small motors and for high pole count machines. If the no load figure is known, either from the manufacturer or by running the motor uncoupled, the load factor is roughly the measured current minus the no load current, divided by the rated current minus the no load current.

Without a no load figure, assume around 30 percent as a working estimate and treat the result as indicative rather than precise.

The method is least reliable below about 40 percent load, which is unfortunately exactly where the important decisions are. It is best used as a screening tool to identify which motors deserve a proper power measurement.

Method three, slip measurement

An induction motor slows as it is loaded, and the relationship between slip and torque is close to linear over the normal operating range.

Measure actual shaft speed with an optical or contact tachometer. Calculate synchronous speed from the supply frequency and pole count, which is 3000 revolutions per minute for two poles at 50 hertz, 1500 for four poles, 1000 for six and 750 for eight.

Actual slip is synchronous speed minus measured speed. Rated slip is synchronous speed minus the nameplate speed. Load factor is actual slip divided by rated slip.

The advantage is that it needs no electrical access at all and no electrical qualification, only a clear view of the shaft or a reflective mark on it.

The disadvantages are real. Slip is small in absolute terms, often only 40 to 60 revolutions per minute at full load, so a tachometer reading a few revolutions out introduces a large percentage error. Supply voltage affects slip, so a reading taken when the voltage is low will overstate the load. The method does not work at all on a motor fed by a frequency converter, since the supply frequency is not fixed.

Despite that, on a direct online motor with a reasonable tachometer it gives a serviceable answer in a few minutes.

Reading the drive, when there is one

Where a frequency converter is fitted, it already knows. Most drives display output power, output current and estimated torque as a percentage of motor rating, and many will log those values.

This is the easiest and often the best measurement available, and it costs nothing. It does depend on the motor parameters having been entered correctly during commissioning, which is worth verifying before trusting the numbers.

Measuring over the right period

Whatever method is used, a single reading describes one moment. Processes vary across a shift, across a week and across a season.

The useful outputs are the average load, which determines energy consumption, and the peak load, which determines the required rating. A motor averaging 35 percent but peaking at 95 percent during a short cycle cannot be replaced with a smaller machine, even though its average suggests otherwise.

Logging over at least one full production cycle, and preferably a week, separates those two cases. Many power meters and most drives can log automatically, so the cost is a little planning rather than a lot of time.

Turning the measurement into a decision

Above 75 percent average load, the motor is correctly sized and the only question is efficiency class at next replacement.

Between 50 and 75 percent, the sizing is reasonable. Leave it alone and revisit at failure.

Between 35 and 50 percent, note it for reassessment at failure, when a smaller motor should be considered.

Below 35 percent on a motor running long hours, calculate the case for immediate replacement with a correctly sized machine. This is where both efficiency and power factor penalties are largest.

In every case, check the peak before specifying anything smaller, and check the starting requirement, since a motor sized for a difficult start will always appear lightly loaded in normal running.