IE1 to IE5 efficiency classes explained in plain terms

Efficiency classes are the shorthand everyone uses when discussing motors, and almost everyone uses them slightly wrongly. The classes are not fixed efficiency percentages, they are not directly comparable between different motor sizes, and the gap between one class and the next is not what the numbers suggest.

What the classes are

The international standard IEC 60034-30-1 defines efficiency classes for single speed motors. There are five.

  • IE1 standard efficiency
  • IE2 high efficiency
  • IE3 premium efficiency
  • IE4 super premium efficiency
  • IE5 ultra premium efficiency

The standard defines, for each class, a minimum efficiency at rated output for every combination of rated power and pole count. So a class is not a number, it is a table.

The step between classes is defined by losses

This is the part that changes how the classes should be read. Each step up is intended to reduce total losses by roughly 20 percent relative to the class below, not to raise efficiency by a fixed number of points.

For a small motor with efficiency around 80 percent, losses are 20 percent of input, so a 20 percent cut in losses raises efficiency by about 4 points. For a large motor already at 95 percent, losses are 5 percent, so the same relative cut raises efficiency by about one point.

That is why the class thresholds converge as power rises. At 0.75 kilowatts the difference between IE2 and IE3 is several percentage points. At 200 kilowatts it is a fraction of a point.

It is also why the absolute energy saving from a class step is larger on big motors despite the smaller percentage difference, because one percent of 200 kilowatts is a great deal more than four percent of 0.75.

Pole count matters

A two pole motor and an eight pole motor of the same rated power have different thresholds for the same class. Slower motors are inherently less efficient for a given output because they need more material and more magnetic circuit to produce the same power at lower speed.

The practical consequence is that comparing the class labels of two motors with different pole counts tells you almost nothing. An IE3 eight pole motor may well have lower absolute efficiency than an IE2 two pole motor of the same rating, and both statements are correct.

When comparing real options, compare the published efficiency percentages at the rating and speed actually required.

How the classes map to technology

IE1 and IE2 are achievable with conventional induction motor design, using better steel, more copper and improved manufacturing.

IE3 is the current baseline for most three phase motors in Europe and is still comfortably within induction motor territory, at the cost of more material and usually a slightly larger frame or a heavier machine.

IE4 pushes induction design close to its practical limit. It is achievable as an induction motor but the machine becomes expensive and heavy, which is why many IE4 offerings use synchronous reluctance or permanent magnet rotors instead.

IE5 is essentially not achievable with a conventional induction rotor. Machines at this class are synchronous, either reluctance or permanent magnet, and they require a frequency converter because they cannot start on a fixed supply. That requirement is the single most important practical fact about IE5.

Where the losses actually are

Understanding what the classes are reducing helps explain the design changes. A motor has five loss categories.

Stator copper losses, from current flowing through winding resistance, are reduced by using more copper and larger slots.

Rotor losses, from current induced in the rotor bars, are reduced by using copper rather than aluminium bars, or eliminated entirely by using a synchronous rotor with no current at all.

Iron losses, from hysteresis and eddy currents in the laminations, are reduced by thinner laminations and better grades of electrical steel.

Friction and windage, from bearings and the cooling fan, are reduced by better bearings and by optimised fan design. Higher efficiency motors run cooler and can sometimes use a smaller fan, which compounds the saving.

Stray load losses, a residual category covering leakage effects, are reduced by better slot design and manufacturing precision.

What the class does not tell you

It is a rated load figure. A motor running at 40 percent load does not achieve its rated efficiency, and the shape of the curve below rated load is not part of the class definition. Higher class motors generally hold efficiency better at partial load, but the class label does not state by how much.

It says nothing about power factor. Higher efficiency does not imply better power factor, and some high efficiency designs have noticeably worse power factor, which affects current and therefore cable and drive sizing.

It says nothing about starting current, which tends to be higher in high efficiency motors because the design changes that reduce losses also reduce impedance.

It says nothing about physical dimensions. A higher class motor of the same rating may be in a larger frame, which matters when replacing a machine in a fixed space.

Reading a real comparison

When two motors are being compared, ignore the class labels and look at four figures. Efficiency at rated load, efficiency at 75 and 50 percent load if published, power factor, and rated current.

Then apply the actual load factor and running hours of the application. A motor that spends its life at 45 percent load should be judged on its efficiency at 45 percent load, and on whether a smaller motor would be a better answer than a more efficient one of the same size.

That last point is worth repeating. Moving a badly oversized motor up an efficiency class treats the symptom. Fitting a correctly sized motor treats the cause and usually saves more.