Harmonics are one of those subjects that stays theoretical until a transformer runs hot, a capacitor bank fails or a generator refuses to accept load. All three usually trace back to the same source, which is the rectifier at the front of every standard frequency converter.
Where the distortion comes from
A standard drive uses a six pulse diode rectifier feeding a capacitor. The capacitor only draws current when the incoming voltage exceeds the voltage already stored on it, which happens twice per cycle per phase and only for a short period around each peak.
The result is that the drive does not draw a smooth sinusoidal current. It draws sharp pulses, and a pulsed waveform is mathematically equivalent to a fundamental sine wave plus a series of higher frequency components. For a six pulse rectifier those components appear at the fifth, seventh, eleventh and thirteenth harmonic, with amplitude falling as order rises.
The drive is doing nothing wrong. This is simply what a capacitor input rectifier does, and it is the price of the isolation that makes converters so useful in the first place.
What harmonic current actually costs
Harmonic currents flow through every component between the drive and the supply transformer, and they cause losses in all of them without doing any useful work.
Transformers suffer most. Losses in the windings rise with the square of frequency because of skin and proximity effects, so a modest harmonic current produces a disproportionate amount of heat. A transformer supplying a heavily distorted load runs hotter than its nameplate loading suggests and ages faster.
Neutral conductors in four wire systems can carry more current than any phase, because triplen harmonics add rather than cancel. This is more of a problem with single phase electronic loads than with three phase drives, but it appears in mixed installations.
Power factor correction capacitors are the most dramatic failure. Capacitor impedance falls as frequency rises, so capacitors act as a sink for harmonic current. Worse, the capacitance combined with the supply inductance forms a resonant circuit, and if that resonance lands near a harmonic present in the load, the circulating current can be several times the expected value. Capacitor banks that fail repeatedly on sites with many drives are almost always a resonance problem.
Generators are more sensitive than the mains because their source impedance is much higher. A distorted current drawn from a generator produces a correspondingly distorted voltage, which affects everything else connected. Standby generator sizing on a site with many drives frequently has to allow for this.
How much distortion is acceptable
The usual reference is total harmonic distortion, expressed either for current or for voltage. Voltage distortion is what affects other equipment, and it is the product of the harmonic current and the supply impedance.
That relationship explains why the same drives cause problems on one site and not another. A factory fed from a large transformer with a short, heavy supply has low source impedance, and even substantial harmonic current produces little voltage distortion. A small workshop on a long rural feeder has high source impedance and the same drives can produce visible voltage distortion.
The practical question is therefore not how much distortion a drive produces, but what share of the total site load is drives and how stiff the supply is. A single 7.5 kilowatt drive on a 1000 kilovolt ampere supply needs no mitigation at all. Twenty drives making up most of the load on a 250 kilovolt ampere transformer needs a plan.
The cheapest effective measure
A line reactor, also called an input choke, fitted in series ahead of the drive is the standard first step. It slows the rate at which the capacitor can charge, which spreads the current pulse over a longer period and reduces its harmonic content.
A reactor of around three percent impedance typically cuts current distortion from something near 80 percent down to the region of 35 to 40 percent. It costs very little, takes almost no cabinet space and has the useful side effect of protecting the drive from supply transients.
Many drives include a DC link choke instead, fitted between the rectifier and the capacitor. It achieves a similar result. Checking whether a drive already has one avoids paying for the same function twice.
Passive filters
A passive harmonic filter is a tuned combination of inductance and capacitance designed to present low impedance at a specific harmonic, giving that current a path that does not flow back into the supply.
They are effective and reasonably economical for larger drives, and they can bring current distortion into the region of five to ten percent. The drawbacks are that they are tuned to a particular frequency, they add capacitance which affects power factor at light load, and they are physically large.
They suit installations with a small number of large drives and a stable load pattern better than installations with many small drives that switch on and off.
Multi pulse rectifiers
Using a phase shifting transformer to feed two or more rectifier bridges at different phase angles causes several harmonic orders to cancel. A twelve pulse arrangement eliminates the fifth and seventh, an eighteen pulse arrangement removes more.
This is an elegant solution and was standard practice on large drives for many years. The cost is the transformer, which is expensive, heavy and adds its own losses. It remains common at high powers and is rarely justified below a few hundred kilowatts.
Active front ends and active filters
An active front end replaces the diode rectifier with a controlled switching stage that draws a near sinusoidal current. Distortion falls to a few percent, power factor can be controlled and, usefully, energy can be returned to the supply during braking.
The cost is significantly higher than a standard drive, and the switching stage introduces high frequency components of its own that need filtering. Where regenerative braking is required anyway, as on hoists, centrifuges and test rigs, the economics often work out because the drive is doing two jobs.
An active harmonic filter is the same idea applied to the whole installation rather than one drive. It measures the distorted current and injects a compensating current, cancelling the harmonics at the point of connection. It suits sites with many existing drives where retrofitting individual mitigation is impractical.
A proportionate approach
Fit line reactors or specify DC link chokes on every drive as a default. They are cheap, they roughly halve the problem and they protect the drives.
Measure before spending anything further. A power quality recorder left on the main incomer for a week gives a real answer, including how distortion varies with production pattern. Designing mitigation from calculated worst cases usually leads to over specification.
If power factor correction capacitors are present on a site with substantial drive load, check whether they are detuned. Plain capacitors on a distorted network are the most likely component to fail and the easiest to fix.
Consider mitigation early on new installations rather than after commissioning. Adding a filter to a finished switchroom is far more disruptive than allowing space for one at design stage.