A frequency converter that works perfectly on the test bench can destroy a motor within a year once it is installed with fifty metres of cable between the two. The mechanism is not obvious, it does not show up in commissioning, and it accounts for a large share of premature motor failures on converter driven machines.
Why fast switching creates the problem
Modern insulated gate transistors switch from off to fully on in a fraction of a microsecond. That speed is what makes drives efficient, because the device spends almost no time in the region where it dissipates power.
The consequence is a voltage edge at the drive output that rises extremely steeply. This rate of rise, usually described as dv/dt and expressed in volts per microsecond, is what the motor insulation and the bearings actually experience. The average voltage may be perfectly normal while the edges are severe.
The reflected wave
Any cable is a transmission line. When a steep voltage edge travels along it and reaches a point where the impedance changes abruptly, part of the energy reflects and travels back.
A motor presents a much higher impedance than the cable feeding it, so a large proportion of the pulse reflects at the motor terminals. The reflected wave adds to the incoming one, and in the worst case the terminal voltage reaches close to twice the DC link voltage. On a 400 volt supply, the DC link sits around 565 volts, so peaks approaching 1100 volts can appear at the motor.
Whether this happens depends on cable length relative to the rise time of the edge. If the cable is short enough that the reflection returns before the edge has finished rising, the two overlap and largely cancel. If it is long enough that the reflection returns after the edge is complete, they add.
The critical length falls as switching speed increases, which is why the problem has become more common rather than less. As a rough guide, cables beyond about 30 metres begin to matter and beyond about 100 metres almost always need attention, though the exact figures depend on the drive.
What that does to the winding
A steep pulse does not distribute itself evenly across a winding. Because of the inductance and stray capacitance of the coils, most of the voltage appears across the first few turns nearest the terminals.
Those turns therefore see far higher stress than the average winding voltage suggests, and repeated stress degrades the turn to turn insulation between them. Failures caused this way appear as a short between adjacent turns at the line end of a coil, and a workshop that strips a motor will usually recognise the pattern.
Motors described as inverter duty or with reinforced insulation systems are built specifically for this. They use higher grade wire enamel, additional phase separation and sometimes a graded first coil. On any new installation with a converter, specifying one costs little and removes the issue.
Bearing currents
The three output voltages of an inverter do not sum to zero at every instant, which means there is a common mode voltage between the motor windings and earth that does not exist on a sinusoidal supply.
That voltage couples capacitively to the rotor. The rotor is separated from the stator by the bearings, and a bearing at rest or at low speed conducts through metal to metal contact. Once the shaft turns fast enough for a lubricant film to form, the bearing becomes a capacitor with a very thin dielectric.
When the voltage across that film exceeds its breakdown strength, it discharges through the bearing in a tiny spark. Each discharge melts a microscopic crater in the raceway. Millions of discharges produce first a frosted surface, then the characteristic washboard pattern known as fluting, and finally a noisy bearing and a failed motor.
Larger motors are more affected because the capacitances involved scale with size. Frames above about 100 kilowatts are the usual candidates, though the problem appears on smaller machines with long cables and high switching frequencies.
Practical measures against bearing damage
Insulated bearings, usually with a ceramic coating on the outer ring, break the circuit at the non drive end. This is the standard factory solution and it is effective, provided only one end is insulated so that the current has no alternative path.
Hybrid ceramic rolling elements achieve the same by making the rolling elements themselves non conductive, and they also tolerate poor lubrication better.
Shaft grounding rings provide a low impedance path from shaft to frame through conductive microfibres, giving the current somewhere to go that is not the bearing. They are a practical retrofit on an installed motor and need periodic inspection.
Symmetrical shielded motor cable with the shield bonded at both ends is the measure that addresses the cause rather than the symptom, because it gives common mode current a defined low impedance return path back to the drive instead of forcing it to find one through the mechanical system.
Cable selection matters more than most people expect
Unshielded cable in a converter installation is a false economy. It allows common mode current to return through whatever path it can find, which frequently means through the driven machine, its couplings and any connected instrumentation.
The correct choice is symmetrical three core cable with three separate protective conductors and an overall shield, terminated with 360 degree glands at both ends rather than a pigtail. A pigtail connection has significant inductance at the frequencies involved and largely defeats the purpose of the shield.
Keeping motor cable physically separated from signal and control cable is equally important, since the same edges that cause the electrical problems also radiate interference.
Output filters and when they are justified
An output reactor slows the voltage edge, reducing dv/dt at the motor without removing it. It is compact and relatively inexpensive, and it is usually sufficient for moderate cable lengths.
A dv/dt filter goes further, combining inductance and capacitance to limit both the rate of rise and the peak. A sine filter goes furthest, producing a genuinely sinusoidal output so that the motor sees no pulses at all and standard cable can be used over long distances.
Sine filters are large, expensive and consume some of the available output voltage, which reduces motor torque. They are justified on very long cable runs, on submersible installations and where an existing standard motor cannot be replaced.
What to decide at design stage
Establish the cable length before selecting anything. If it exceeds the drive manufacturer’s stated limit for the chosen switching frequency, the choice is between a filter, a lower switching frequency or moving the drive closer to the motor.
Specify inverter rated motors on any new converter application, and insulated bearings or a grounding ring above roughly 100 kilowatts. Use symmetrical shielded cable with proper 360 degree terminations throughout.
None of these measures are expensive when they are part of the original specification. All of them are expensive when they are fitted after a motor has already failed twice.