A frequency converter that has been installed carefully will usually run for years without attention. One that has been installed in a hurry tends to produce a run of intermittent faults that are difficult to diagnose later, because by then nobody remembers what was done. Commissioning properly the first time is the cheapest maintenance available.
Before power is applied
Check the drive rating against the motor nameplate current, not its kilowatt figure, and confirm the duty rating selected matches the load type. This is the last convenient moment to discover an undersized drive.
Confirm the supply voltage and frequency match the drive specification, and that the supply is capable of the fault level the drive expects.
Inspect the mounting. Drives dissipate heat through their heatsinks and most require specified clearances above and below. A drive mounted tight against a cable trunking or in a sealed cabinet without ventilation is a future thermal trip.
Check the motor cable. It should be symmetrical shielded cable, with the shield terminated through a 360 degree gland at both ends rather than a pigtail. Measure the actual installed length and compare it with the manufacturer’s limit for the intended switching frequency.
Verify earthing. The drive, the motor frame and the cabinet should all be bonded, and the motor earth should return through the cable rather than through the machine structure.
Finally, measure the motor insulation resistance with the drive disconnected. Never megger a motor with the drive connected, because the test voltage will destroy the output stage. Disconnect at the drive terminals first.
First power up with the motor disconnected
Energise the drive with the motor cable disconnected. Confirm the display comes up, the internal fans run and no fault is present.
Set the supply voltage and frequency parameters, and confirm the drive has recognised the incoming supply correctly.
Enter the motor data from the nameplate. Rated voltage, current, frequency, speed, power and power factor. These parameters are the basis of every calculation the drive makes about the motor, and approximate values produce approximate control. Rated speed in particular is often left at a default, which corrupts the drive’s slip compensation.
Motor identification
Most drives offer an automatic tuning routine that measures stator resistance and inductance. Running it makes a noticeable difference to low speed torque and to the accuracy of the drive’s internal motor model.
A static identification, performed with the motor stationary, is usually sufficient and is safe on a coupled machine. A rotating identification is more accurate but turns the shaft, so it must only be run with the load uncoupled or where free rotation is known to be safe.
If the installation includes an output filter, confirm whether identification should be run with it fitted. Some drives require the filter to be accounted for explicitly.
Direction and basic running
Couple the motor and run it briefly at low speed to confirm the direction of rotation before the load can be damaged. On pumps and fans this is critical, because a centrifugal machine running backwards still moves some fluid and can look superficially normal.
If direction is wrong, change it in the drive parameters or by swapping two output phases, and record which was done.
Ramps, limits and protection
Set acceleration and deceleration ramps to match the mechanical reality. Too fast an acceleration demands torque the drive may not have and trips on overcurrent. Too fast a deceleration pushes energy back into the DC link and trips on overvoltage unless a braking resistor is fitted.
Set the minimum speed with cooling in mind. A self ventilated motor on a constant torque load cannot run continuously at very low speed without forced ventilation, and the minimum frequency parameter is what enforces that.
Set the maximum speed deliberately rather than leaving it at a default that may exceed what the driven machine can tolerate.
Configure the motor thermal protection, and connect winding thermistors if the motor has them. The drive’s internal thermal model is an estimate, while a thermistor is a measurement.
Set the current limit to a value appropriate to the load rather than the drive maximum.
Control wiring and stop functions
Verify every control input and output does what the drawing says. Start, stop, reverse, speed reference, run feedback and fault output should each be exercised individually.
Confirm the behaviour of the safe torque off input if one is used, and confirm that removing the run signal produces the intended stop type. A coast to stop and a ramped stop are very different on a machine with a guard interlock.
Check what the drive does on loss of the speed reference signal. The default is often to hold last speed, which may not be what the process requires.
Running under load
Run the machine through its full speed range with the real load, watching for mechanical resonance. Most drives allow speed bands to be skipped, and finding the resonant point during commissioning is far easier than chasing a vibration complaint later.
Record motor current at each significant operating point and compare with the nameplate. A current well above rated at normal production speed means something is wrong with the sizing or the load.
Listen to the motor. Audible noise from switching can usually be reduced by raising switching frequency, but that derates the drive and increases stress on the motor insulation, so it is a trade rather than a free improvement.
Let the installation run for a sustained period and then check drive heatsink temperature, cabinet internal temperature and motor frame temperature. Thermal problems appear after an hour, not after five minutes.
Handover
Save the parameter set. Almost every drive can copy its configuration to a keypad, a memory card or a laptop file, and that file is worth more than any manual when a drive has to be replaced at short notice.
Record the drive type, serial number, software version, motor data and the parameters that were changed from default. Put a copy in the cabinet and another wherever maintenance records are kept.
Finally, note the reason behind any unusual setting. A skip frequency, an extended ramp or a reduced current limit all made sense to whoever set them, and none of that survives unless it is written down.